Electplus Industry - Distributor & Supplier of Flexible Control Cables, Data & Communication Cables, High Temperature Cables, Servo Motor Cables, Fiber Optic Cables, etc.
DRAKA Instrument Cables - LSHF - Overall Screen - Armoured(SWA) CU/XLPE/OSCR/LSHF/SWA/LSHF, 500V to BS EN 50288-7, IEC332-3-22
Category:
Instruments Cable
Quantity:
In Stock
Details
Draka Instrumetation Cables - LSHF - Overall Screen - Armoured(SWA) CU/XLPE/OSCR/LSHF/SWA/LSHF, 500V to BS EN 50288-7, IEC332-3-22
Application
Instrumentation cables are used in data processing andprocess control. The electrostatic screen protect thescreened pairs against outer electrostatic interferencefields. Low level of line attenuations and low mutualcapacitances enable long transmission distances fastpulse acceleration. Instrumentation cables with steel wirearmoured are suitable for fixed installations in damplocations, in open spaces and for underground laying.
Two/Three/Four insulated cores are cabled together and covered with a polyester tape wrapping
Assembly
Multiple pairs/triads/quads are cabled together, supplied with non-hygroscopic filler (optional) to obtain a circular construction and covered with a polyester tape wrapping
Overall Screen
(OSCR), Min. 20% overlap of aluminium backed polyester tape in contact with 0.5mm² (16/0.20mm) tinned annealed drain wire followed by a polyester tape wrapped over the screening tape
Bedding
(LSHF) Low Smoke Halogen Free -Black
Armouring
(SWA) Galvanized Steel Wire Armour
Outer Sheath
(LSHF-AT-AR) Low smoke zero halogen compound with anti-termite and anti-rodent additives. Black (Optional: Blue colour for Intrinsically Safe)
Insulation color
1 pair in Black & White
2 pair & above -each pair in Black & White core with numbering.
1 triad in Black, White & Red
2 triad & a bove –each triad in Black, White & Red printed with numbering.
Technical Data
Reference Standard
BS EN 50288-7
Voltage
500V
Max Operating Temperature
+90ºC
Halogen Free
IEC 60754
Low Smoke Emission
IEC 61034
Flame Retardant
IEC 60332-3-22
Max. Conductor Resistance
≤7.6Ω/km at 20°C(2.5mm²)
≤12.3Ω/km at 20°C(1.5 mm²)
≤18.4Ω/km at 20°C(1.0 mm²)
≤26.5Ω/km at 20°C(0.7 5mm²)